The WCOMP compensation units are the ideal choice when sensitive components must be installed outdoors.
Medium voltage components and control are installed in a stainless steel station building to protect them from inclement weather. This system type is often used as central compensation, e.g., of wind farms, as tele command blocking filter for grid link-up or as harmonic filter.
The housing dimensions vary from 1.8 to 7 meters in length and the maximum power is approx. 7 Mvar (10 kV). As with the R-, E-, and SCOMP series, the WCOMP also comes in three versions: WCOMP-F as fixed step with external actuation and without own switching device, WCOMP-E as externally controlled unit with integrated contactor, and WCOMP-A as automatically controlled system with integrated control and monitoring functions.
In addition, four standard reactors versions are available for this series: LINR (inrush current limiting reactor), 7 % (189 Hz), tele command blocking filter application or as filter for several harmonics.
In addition to the standard solutions, the WCOMP system is ideal for customized projects and modifications.
FEATURES
Operating voltage | 1 kV - 20 kV* |
Control voltage | 230 VAC/ 220 VDC (fused)* |
Nominal frequency | 50 / 60 Hz |
Insulation level | 20 / 60 kV |
28 / 75 kV | |
38 / 95 kV | |
Nominal power | 150 kvar to 7000 kvar* |
Capacitor types | B series (B01-B03) |
(3-phase capacitors + pressure switch) | |
C series (C03) | |
(capacitors with 2 power sections + unbalance monitoring) | |
E-/G series (E06, G06) | |
(three-phase capacitors + unbalance monitoring) | |
Design versions | -F (fixed step) |
-E (with contactor for external actuation) | |
-A (system with automatic control) | |
Tuned frequency | 189 Hz (7 %)* |
210 Hz (5,67 %)* | |
LINR inrush current limiting reactor | |
Protection | IP34D* |
Ambient temperature | –20 °C to 40 °C* |
Installation site | Outdoor |
Altitude | < 1000 m above sea level |
Impregnating material | Faradol / Jarylec |
Norm | IEC 60871-1 / IEC 60071 / IEC 60282-1 / VDE 101 |
Finish | RAL 7032 |
Dimensions (W x D x H) | om request |
Optional | Discharge transformer, heating, lighting, voltage transformer, definite-time overcurrent-time protection, pressure relief flaps (roof), forced ventilation, double locking system, cable grounding electrode, incoming disconnector, etc. |
*Other versions available on request |