Scope of application

The choked modular units CLMM-X-L and CDMM-X-L in the modular system with filter circuit reactors are used as central compensation systems in networks subject to harmonic loads. The CLMM-X-L and CDMM-X-L modular systems are designed for medium to large reactive power reactive power demand. They are specially designed for variable They are especially suitable for variable adjustment of the step power or the system power.

Description

The ready-to-connect modular systems CLMM-X-L and CDMM-X-L are designed as a cabinet system. Each cabinet unit has a separate from below and contains modules with mounted capacitors and upstream and upstream reactors. All functional units belonging to the control control system are integrated in the cabinet system. The reactive power controller is only required once for all connected connected enclosure units. It switches the compensation power on or off in steps on or off.

Advantages

















Schutzart: IP 00, 50 Hz Drehstrom
















Nennleistung
kvar 1)

Bestellbezeichnung

Kerntyp Anschluss-
kennung *

Maße
(B x T x H)
mm
Gewicht

ca. kg
Artikel-
Nummer

















Anlagennennspannung 400V, 50 Hz Drehstrom, Verdrosselung: p=5,67% (fr = 210 Hz), Standardauslegung
















2,5
Drossel - 400/50 - 2,5 - L057/S

75/25 1 150 x 95 x 150 5 K049 - 1 8 2
5
Drossel - 400/50 - 5 - L057/S

90/30 1 180 x 105 x 180 7 K049 - 1 8 3
6.25
Drossel - 400/50 - 6,25 - L057/S

90/50 1 180 x 125 x 180 10 K049 - 2 2 7
7,5
Drossel - 400/50 - 7,5 - L057/S

90/50 1 180 x 125 x 180 10 K049 - 1 8 4
10
Drossel - 400/50 - 10 - L057/S

114/38 2 230 x 125 x 220 13 K049 - 1 8 5
12,5
Drossel - 400/50 - 12,5 - L057/S

114/38 2 230 x 125 x 220 14 K049 - 1 8 6
15
Drossel - 400/50 - 15 - L057/S

114/62 3 230 x 150 x 220 20 K049 - 2 0 1
20
Drossel - 400/50 - 20 - L057/S

114/62 3 230 x 150 x 220 18 K049 - 2 0 2
25
Drossel - 400/50 - 25 - L057/S

120/61 3 240 x 150 x 220 19 K049 - 2 0 3
30
Drossel - 400/50 - 30 - L057/S

150/50V 3 300 x 160 x 240 23 K049 - 2 0 4
37,5
Drossel - 400/50 - 37,5 - L057/S

132/72 3 265 x 175 x 240 28 K049 - 7 7 2
40
Drossel - 400/50 - 40 - L057/S

150/75V 3 300 x 180 x 240 33 K049 - 2 0 5
50
Drossel - 400/50 - 50 - L057/S

150/75V 3 300 x 180 x 240 35 K049 - 2 2 2
















Anlagennennspannung 400V, 50 Hz Drehstrom, Verdrosselung: p= 5,67% (fr = 210 Hz), verstärkte Auslegung
















25
Drossel - 400/50 - 25 - L057/V

150/75V 3 300 x 180 x 240 34 K049 - 7 0 1
50
Drossel - 400/50 - 50 - L057/V

150/90LL 3 300 x 205 x 330 54 K049 - 7 0 2
















Anlagennennspannung 400V, 50 Hz Drehstrom, Verdrosselung: p= 5,67% (fr = 210 Hz), erhöhte Linearität
















25
Drossel - 400/50 - 25 - L057/L

150/60V 3 300 x 165 x 240 28 K049 - 7 1 2
50
Drossel - 400/50 - 50 - L057/L

150/103 3 300 x 215 x 270 50 K049 - 7 1 3
















Anlagennennspannung 525V, 50 Hz Drehstrom, Verdrosselung: p= 5,67% (fr = 210 Hz), Standardauslegung
















12,5
Drossel - 525/50 - 12,5 - L057/S

114/38 2 230 x 125 x 220 13 K049 - 2 3 1
25
Drossel - 525/50 - 25 - L057/S

120/71 3 240 x 160 x 220 22 K049 - 2 3 5
50
Drossel - 525/50 - 50 - L057/S

150/75 3 300 x 180 x 270 37 K049 - 2 3 9
















Anlagennennspannung 690V, 50 Hz Drehstrom, Verdrosselung: p= 5,67% (fr = 210 Hz), Standardauslegung
















12,5
Drossel - 690/50 - 12,5 - L057/S

114/38 4 230 x 125 x 220 13 K049 - 2 6 7
25
Drossel - 690/50 - 25 - L057/S

120/71 3 240 x 160 x 220 22 K049 - 2 7 1
50
Drossel - 690/50 - 50 - L057/S

150/90V 3 300 x 195 x 240 39 K049 - 2 7 5
















Anlagennennspannung 400V, 50 Hz Drehstrom, Verdrosselung: p= 7% (fr = 189 Hz), Standardauslegung
















2,5
Drossel - 400/50 - 2,5 - L070/S

75/25 1 150 x 95 x 150 4 K049 - 1 9 9
5
Drossel - 400/50 - 5 - L070/S

75/40 1 150 x 110 x 150 6 K049 - 1 9 7
6.25
Drossel - 400/50 - 6,25 - L070/S

90/30 1 180 x 105 x 180 7 K049 - 2 2 6
7,5
Drossel - 400/50 - 7,5 - L070/S

90/50 1 180 x 125 x 180 10 K049 - 2 0 0
10
Drossel - 400/50 - 10 - L070/S

90/50 1 180 x 125 x 180 10 K049 - 0 5 0
12,5
Drossel - 400/50 - 12,5 - L070/S

90/50 2 180 x 125 x 180 11 K049 - 1 9 8
15
Drossel - 400/50 - 15 - L070/S

114/62 3 230 x 150 x 220 20 K049 - 1 9 2
20
Drossel - 400/50 - 20 - L070/S

114/62 3 230 x 150 x 220 18 K049 - 0 5 1
25
Drossel - 400/50 - 25 - L070/S

114/62 3 230 x 150 x 220 18 K049 - 2 3 0
30
Drossel - 400/50 - 30 - L070/S

120/71 3 240 x 160 x 220 22 K049 - 0 5 3
37,5
Drossel - 400/50 - 37,5 - L070/S

132/72 3 265 x 175 x 240 27 K049 - 7 7 6
40
Drossel - 400/50 - 40 - L070/S

132/72 3 265 x 175 x 240 27 K049 - 7 7 8
50
Drossel - 400/50 - 50 - L070/S

150/75V 3 300 x 180 x 240 34 K049 - 2 2 1
















Anlagennennspannung 400V, 50 Hz Drehstrom, Verdrosselung: p= 7% (fr = 189 Hz), verstärkte Auslegung
















25
Drossel - 400/50 - 25 - L070/V

150/60V 3 300 x 165 x 240 27 K049 - 7 0 3
50
Drossel - 400/50 - 50 - L070/V

150/90 3 300 x 195 x 270 45 K049 - 7 0 4
















Anlagennennspannung 400V, 50 Hz Drehstrom, Verdrosselung: p=7% (fr = 189 Hz), erhöhte Linearität
















25
Drossel - 400/50 - 25 - L070/L

132/72 3 265 x 175 x 240 26 K049 - 7 1 4
50
Drossel - 400/50 - 50 - L070/L

150/90V 3 300 x 195 x 240 40 K049 - 7 1 5
















Anlagennennspannung 525V, 50 Hz Drehstrom, Verdrosselung: p= 7% (fr = 189 Hz), Standardauslegung
















12,5
Drossel - 525/50 - 12,5 - L070/S

90/50 4 180 x 125 x 180 11 K049 - 2 3 2
25
Drossel - 525/50 - 25 - L070/S

114/62 3 230 x 150 x 220 21 K049 - 2 3 6
50
Drossel - 525/50 - 50 - L070/S

150/75 3 300 x 180 x 270 33 K049 - 2 4 0
















Anlagennennspannung 690V, 50 Hz Drehstrom, Verdrosselung: p=7% (fr = 189 Hz), Standardauslegung
















12,5
Drossel - 690/50 - 12,5 - L070/S

114/38 4 230 x 125 x 220 12 K049 - 2 6 8
25
Drossel - 690/50 - 25 - L070/S

132/72V 3 265 x 155 x 200 22 K049 - 2 7 2
50
Drossel - 690/50 - 50 - L070/S

150/75V 3 300 x 180 x 240 33 K049 - 2 7 6
















Zubehör
































Befestigungs- und Anschlussschrauben für 1 Drossel







B122- O M Z
















1) Die Nennleistung ergibt sich durch die Reihenschaltung der Drossel mit dem zugehörigen Kondensator.
Andere Auslegungen sind auf Anfrage möglich
















Hinweis:














Anlagen, die nicht für Verdrosselung vorbereitet sind, können nicht nachträglich verdrosselt werden, da die Kondensatoren eine höhere Auslegespannung benötigen!
















* Anschlusskennung:
1 = Klemmen 4 mm²
2 = Klemmen 10 mm²
3 = Cu-Schiene 20 x 3 mm, Lochdurchmesser 9 mm
4 = Ringkabelschuhe, Lochdurchmesser 6,5 mm